Operation:
Troubleshooting guide
Troubleshooting guide.
Problem
number
Problem Possible cause Action
13
14
15
16
17
18
19
ML probe fault
Replace probes fault
Probe assembly fault
Temperature sensor
fault
Thermal trip fault
SDU fault
EEPROM fault
Improper water level
changes inside the
tank
Dirty probes
Deterioration of probe
rod assembly
Open, shorted, or
incorrect wiring of
sensor
Unit has overheated.
SDU blower or AFPS
is incorrectly wired.
SDU blower motor is
defective (SDU fan
does not start).
Internal program
changed
(VAPOR-LOGIC
3
detected a change
from its previous
program check)
Verify proper wiring of probe system.
Clean or replace probe rod assembly.
Rewire probes using nonshielded 18-
gauge wire routed in conduit separate
from power wiring.
Check that wiring between control
cabinet and humidifier does not exceed
the recommended 50-foot limit.
Check for plumbing problems.
Clean probes.
Replace probe rod assembly.
Check wiring terminals
(VAPOR-LOGIC
®
3
terminal J25) for
correct wiring and voltages.
Check for proper water level in tank.
Check SDU for proper wiring.
Replace SDU blower.
Consult DRI-STEEM for
reprogramming instructions.
More on next page ...