Page 8 DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
S p e c i f i c a t i o n s , c a p a c i t i e s , a n d
w e i g h t s
Capacity notes
• At sea level, approximately 152 Btu are required to raise the
temperature of one pound of water from 60 °F to 212 °F. (At sea
level, approximately 352 kJ are required to raise the temperature
of one kilogram of water from 16 °C to 100 °C.)
• An additional 970 Btu are required to change the state of one pound
of 212 °F water to vapor. (An additional 2257 kJ are required to
change the state of one kilogram of 100 °C water to vapor.)
• Another factor to consider is condensation steam loss from
piping. Use the following general steam loss guidelines:
– Vapor hose: 0.15 lbs/hr/ft (0.22 kg/h/m)
Insulated pipe: 0.05 lbs/hr/ft (0.07 kg/h/m)
Hard pipe and dispersion tubes: 0.50 lbs/hr/ft (0.7 kg/h/m)
High-eciency dispersion tubes: 0.20 lbs/hr/ (0.298 kg/h/m)
For more detailed information about condensation steam loss, see
the DRI-STEEM Design Guide or our software program, Dri-calc.
LP gas
All models operate at rated input.
High altitude
An input derate exists when operating units at a high altitude. See
Table 8-2 for high altitude derate information.
* GTS-400 models are derated 10% from 2001-4500 ft in Canada.
Table 8-1:
GTS specifications, capacities, and weights for North American models only
GTS
model
Maximum
steam
capacity
Input
Water usage
at maximum
capacity**
Tank
volume
GTS GTS with outdoor enclosure
Full load
amps*
Operating
weight
Shipping
weight
Operating
weight
Shipping
weight
lbs/hr kg/h MBh kW m
3
/h
gals/
hr
litres/
hr
gals litres lbs kg lbs kg lbs kg lbs kg
120 V
60 Hz
230 V
50 Hz
GTS-100 75 34 100 29 2.76 9 34.1 48 181.7 700 320 375 170 800 365 500 230 1.8 2.8
GTS-200 150 68 200 59 5.52 18 68.1 48 181.7 700 320 375 170 800 365 500 230 1.8 2.8
GTS-300 225 102 300 88 8.28 27 102.2 52 196.8 850 385 450 205 1000 455 600 270 3.0 4.0
GTS-400 300 136 400 117 11.04 36 136.3 52 196.8 850 385 450 205 1000 455 600 270 3.0 4.0
GTS-500 375 170 500 147 13.80 45 170.3 76 287.7 1100 500 600 270 1450 660 950 430 4.5 5.5
GTS-600 450 204 600 176 16.56 54 204.4 76 287.7 1100 500 600 270 1450 660 950 430 4.5 5.5
GTS-700 525 238 700 205 19.32 63 238.5 89 336.9 1400 635 700 320 1750 795 1050 475 6.0 7.0
GTS-800 600 272 800 234 22.08 72 272.5 89 336.9 1400 635 700 320 1750 795 1050 475 6.0 7.0
* Add 15 full load amps for outdoor enclosure heater load on all GTS models, add 1 full load amp for an outdoor enclosure without heaters.
** Add 10% to account for skim and automatic drain/flush features if utilized (standard water units only).
Table 8-2:
High altitude derate
Altitude
Input
derate %
feet meters
0–2000 0–610 0
2001–2500 610–765 2*
2501–3000 765–915 4*
3001–3500 915–1065 6*
3501–4000 1065–1220 8*
4001–4500 1220–1370 10
4501–5000 1370–1525 12
5001–5500 1525–1675 14
5501–6000 1675–1830 16
6001–6500 1830–1980 18
6501–7000 1980–2135 20
7001–7500 2135–2285 22
7501–8000 2285–2440 24
I m p o r t a n t : See Pages 76-77 for
additional European model specifications
and capacity notes.