49
Service interval, EOS, date set.
Operation
Operation:
Service interval, EOS, date set
Service interval
The VAPOR-LOGIC
®
3
controller keeps track of how
much water has been converted to steam. After a
user-defined number of pounds/kilograms have been
boiled, a service humidifier message will appear on
the keypad/display. However, the humidifier will
continue to operate after the message appears. The
message is simply to notify the user that the service
interval has been reached. This service interval is
adjustable through the Set Up screen on the keypad/
display.
End of season drain
If there is no call for humidity for a preset time
period, the humidifier will be placed in End of
Season (EOS). When the unit enters End Of Season,
the humidifier is placed in Standby Mode. The drain
valve is held open for one hour to allow the tank to
drain and then it is closed. If the humidifier receives
a call for humidity after the end-of-season drain, it
automatically leaves the Standby Mode and returns to
the Auto Mode. The tank is refilled and the
humidifier resumes normal operation. The amount of
inactivity time that is needed before the humidifier
enters End Of Season is adjustable through the Set
Up screen on the keypad/display (Inactivity Until
EOS). This option is only available on units that are
equipped with automatic drain and fill valves.
Setting date and time
The VAPOR-LOGIC
3
controller contains a real-time
clock that is used for several features including the
drain and flush sequence and the logging of alarms.
If it becomes necessary to reset the date or time, they
are accessible through the Set Up screen on the
keypad/display.