P a g e 4 2 D R I - S T E E M D e s i g n G u i d e
D R I - S T E E M D e s i g n G u i d e P a g e 4 3
6. Valve (heat exchanger systems)
Upon a call for humidity, valves allow steam (STS), hot water
(LTS), or an air/gas mixture (GTS) to enter the heat exchanger.
7. Temperature sensor
Systems with VAPOR-LOGIC3 have a temperature sensor
mounted on the evaporating chamber enabling:
Over-temperature protection (electric systems)
Freeze protection
Preheating, allowing rapid response to a call for humidity
8. Service access
Access cover and cleanout plates allow periodic inspection and
servicing of the evaporating chamber.
9. Steam outlet
Steam generated in the evaporating chamber rises and exits
through the steam outlet and travels to the dispersion unit
through either vapor hose or piping. See Page 46 for steam
outlets available on DRI-STEEM humidifiers.
Figure 43-1:
STS Steam-to-Steam system
2
3
4
5
6
7
8
9