DIGITAL DISPLAY/KEY PAD TROUBLE SHOOTING GUIDE
PROBLEM POSSIBLE CAUSE RECOMMENDED ACTION
VAPOR-LOGIC RED
INDICATOR LIGHT
IS OFF
No control voltage present Check for proper supply voltage.
Heater fuses open Check heater fuses for voltage present at transformer.
Transformer secondary
circuit breaker tripped
Check wiring for shorts; reset breaker.
Disruption in microprocessor
logic
Verify proper control cabinet wiring. Press "RESET"
button to reset VAPOR-LOGIC control board.
VAPOR-LOGIC RED
INDICATOR LIGHT
ON
CONTINUOUSLY
VAPOR-LOGIC
microprocessor disrupted
Verify proper control cabinet wiring. Press "RESET"
button to reset VAPOR-LOGIC control board.
VAPOR-LOGIC RED
INDICATOR LIGHT
BLINKING ON-OFF
(heartbeat)
Normal operation
VAPOR-LOGIC
GREEN
INDICATOR LIGHT
OFF
Low water in evaporating
tank
Check water supply valve is open. System in end of
season drain. Low conductivity water (probe system). DI
float switch defective or incorrect wiring.
VAPOR-LOGIC
GREEN INDICATOR
LIGHT ON
Normal operation Sufficient water in tank.
Caution If light is "on" without water in tank, turn off, check wiring,
and consult DRI-STEEM.
INDICATOR LIGHT
BLINKING ON-OFF
(long/short pulses)
Indicates fault condition See Fault Chart beginning on page 38 for more
information. Identify the fault, turn power off, repair,
restart.
NO REMOTE FAULT
INDICATION
Field wiring not installed Provide field wiring to a remote fault indicator from
VAPOR-LOGIC terminal block J7.
Field supplied remote fault
indicator lamp burned out
Check if lamp is burned out and replace.
Remote fault
VAPOR-LOGIC relay not
switching
Check relay continuity (VAPOR-LOGIC terminal J7) for
contact closure.
NO READABLE
INFORMATION
DISPLAYED ON
KEYPAD
No power to VAPOR-LOGIC
board
Check main supply power.
(Continued on
next page.)
Check control transformer secondary manual reset
circuit breaker.
Modular communication
cable disconnected
Connect modular cable.
®